**Lead time of 6-12 weeks, an estimate only and subject to factory confirmation after order.
- Honeywell Gas Turbine flame monitoring systems
- The Honeywell LG/EG flame monitoring system detects the UV radiation emitted by a hydrocarbon flame and produces an output signal to indicate a flame or noflame condition. This system has delivered
- proven performance on General Electric (and GE licensee) gas turbines for more than 35 years.
- Geiger Mueller-type sensor phototube. Detects UV radiation in the 180..260nm range of the spectrum. Solar blind and tolerant to black body radiation.
- Two-year shelf-life, 10000h MTBF with over one billion (109) operating hours.
- Gas Turbines for power genaration and compressors
- Temperature range: -40...176C
- Hardware outputs: For EG1033 amplifier modules only
- EG1033AA: Transistor open collector
- EG1033AB and EG1033AC: Relay contacts (SPDT)
- Features: High sensitivity with fast Flame Present Response Time (0.1 sec typical)
- Flame Loss Response Time: 0.2 sec max.
- Amplifiers support multiple voltage requirements: 28 Vdc, 20-35 Vdc and 115 Vac.
- Operating distances up to 330m (1000ft), sensor to amplifier.
- Qualified component on General Electric turbines.
- Available with European Directive CE mark for EMC 89/336/EEC, LVD 73/23/EEC and ATEX Explosive Atmosphere 94/9/EC (EEx d IIA T3 or EEX d IIC T3, Zone 1 and 2).
- Available with Factory Mutual approval for explosive atmospheres (Class I, Div 1 and 2, Groups B, C and D).
- Note: Honeywell LG1093 series may not work like expected on GE/NP DLE gas turbines (Low-NOx). These need pre-selected LG1093's that are not available via Honeywell
- Flame Sensor with 3/4 inch internal NPT mounting and Teflon shielded cable with 1" external conduit thread. Viewing window rated for 10bar (150psi).
- Model: Cable length 61ft (12.8m)
- Supply voltage: no
- Approvals: CE/ATEX (EEx d IIA T3)
- UV Sensor Cross Reference: GE 261A1812P14